Conventional primary-side liquid cooling suffers heavy on-site work and long lead times. ZTE liquid cooling EDU bridges outdoor cold sources and indoor CDUs. Cooling capacity: 300–1200kW (customizable to 3000kW), fully integrated all-in-one unit. Rated for -40℃~55℃ outdoor direct mounting; dual power supply guarantees steady fluid flow. Factory prefabrication cuts delivery cycles, delivering robust, low-maintenance primary liquid cooling for new and retrofit facilities.
Outdoor-Grade Skid Unit
Integrated Prefabrication
Full-Link Redundancy
Easy O&M
| ZXETM P300/P1200 Liquid Cooling EDU | Product Parameters | |
|---|---|---|
| Cooling Capacity | ZXETM P300(300W) ZXETM P1200 (1500W) |
|
| Primary Supply Temp. | 35℃ | |
| Primary Return Temp. | 45℃ | |
| Flow Rate | ZXETM P300(30m³/h) ZXETM P1200(121m³/h) |
|
| Fluid Supply Pressure | ZXETM P300(250kPa) ZXETM P1200(230kPa) |
|
| Noise Level | ZXETM P300(67dB(A)) ZXETM P1200(75dB(A)) |
|
| L × W × H | ZXETM P300(1400×980×1600mm) ZXETM P1200(2000×1460×1920mm) |
|
| Net Wt. | ZXETM P300(550kg) ZXETM P1200(1700kg) |
|
| Color | Gray | |
| Primary Supply / Return | ZXETM P300(3" Chuck, ISO2852) ZXETM P1200(DN150 Flange) |
|
| Cold Source Supply / Return | ZXETM P300(3" Chuck, ISO2852) ZXETM P1200(DN150 Flange) |
|
| Power Phases | 3P | |
| Op. Voltage | 380V±10% | |
| Freq. | 50±2.5Hz | |
| Max. Op. Current | ZXETM P300(21A) ZXETM P120(52A) |
|