Tackling rising computing density in AI computing centers and the downsides of standalone air and liquid cooling systems — duplicated investment, siloed O&M and high upgrade costs — ZTE ZXETM Dual-Cold-Source FWU is a core air-liquid integrated cooling solution for AI facilities. Covering 60kW near-end thin-plate units and 120–250kW remote large FWUs, it leverages an innovative air-liquid homologous architecture and 3-mode AI control to enable seamless evolution from full air to full liquid cooling for all power density scenarios.
3-Mode AI Optimization
Air-Liquid Homology
Full Form Factor Adaptability
High-Reliability Design
| ZXETM F120F/F150F/F200F/F250F Dual-Cold-Source Room-Level FWU | Product Parameters | |
|---|---|---|
| Net Sensible Cooling | ZXETM F120F (120kW) ZXETM F150F (150kW) ZXETM F200F (200kW) ZXETM F250F (250kW) |
|
| Supply Air Temp./RH | 25℃/50% | |
| Return Air Temp./RH | 38℃/24% | |
| Supply Water Temp. | 34℃ | |
| Return Water Temp. | 42℃ | |
| Rated Air Flow | ZXETM F120F (27400m³/h) ZXETM F150F (34300m³/h) ZXETM F200F (45700m³/h) ZXETM F250F (57100m³/h) |
|
| Fan Type | EC | |
| Ext. Static Pressure | 150Pa | |
| Rated Pwr. | ZXETM F120F (18.8kW) ZXETM F150F (23.5kW) ZXETM F200F (31.3kW) ZXETM F250F (39.1kW) |
|
| W×D×H | ZXETM F120F (2500×1300×2500mm) ZXETM F150F (2500×1300×2500mm) ZXETM F200F (2500×1300×2800mm) ZXETM F250F (3000×1300×2800mm) |
|
| Net Wt. | ZXETM F120F (1000kg) ZXETM F150F (1250kg) ZXETM F200F (1700kg) ZXETM F250F (2080kg) |
|
| Water Connection Size | ZXETM F120F (DN65) ZXETM F150F (DN80) ZXETM F200F (DN80) ZXETM F250F (DN100) |
|
| Control Interface | Modbus , SNMP | |
| Op. Voltage | 380V±10% | |
| Freq. | 50Hz±2.5Hz | |
| Configuration | Integrated ATS, dual power supply | |