For mid-to-large data centers with 15–20℃ high-temperature chilled water, traditional air cooling suffers from low efficiency, slow deployment, complex O&M and difficult retrofits. ZTE ZXETM Series Chilled Water FWU is a room-level remote air supply cooling solution for large cloud and carrier facilities. With 210–500kW cooling capacity, it features blow-through positive pressure design and PICV smart water control to optimize heat exchange efficiency and full-lifecycle O&M.
Prefabricated Modularity
High-Efficiency Heat Exchange
Intelligent Control
All-Round Reliability
| ZXETM F210/F230/F250 Chilled Water FWU | Product Parameters | |
|---|---|---|
| Net Sensible Cooling | ZXETM F210(210kW) ZXETM F230(230kW) ZXETM F250(250kW) |
|
| Supply Air Temp./RH | 25℃/54% | |
| Return Air Temp./RH | 38℃/26% | |
| Supply Water Temp. | 20℃ | |
| Return Water Temp. | 30℃ | |
| Rated Air Flow | ZXETM F210(50000m³/h) ZXETM F230(54000m³/h) ZXETM F250(58000m³/h) |
|
| Fan Type | EC | |
| Ext. Static Pressure | 150Pa | |
| Rated Pwr. | ZXETM F210(10.5kW) ZXETM F230(12.1kW) ZXETM F250(13.2kW) |
|
| W×D×H | ZXETM F210,ZXETM F230(2300×1600×3000mm) ZXETM F250(2300×1600×3600mm) |
|
| Net Wt. | ZXETM F210,ZXETM F230(2500kg) ZXETM F250(2700kg) |
|
| Water Connection Size | DN65 | |
| Control Interface | Modbus-TCP, SNMP | |
| Op. Voltage | 380V±10% | |
| Freq. | 50Hz±2.5Hz | |
| Configuration | Integrated ATS, dual power supply | |