Simpler Structure Design - Only need one cabinet to support 24KW output capacity and 2groups 12V Lead Acid battery or 4PCS 3U lithium battery, satisfy 3G/4G/5G co-site and sharing site power supply requirement. Compared with traditional site power system, save 50% site footprint - Unified power platform and key components with modular design, support smooth evolution for future 5G and low-carbon application
Highlights
Simpler Structure Design
- Only need one cabinet to support 24KW output capacity and 2groups 12V Lead Acid battery or 4PCS 3U lithium battery, satisfy 3G/4G/5G co-site and sharing site power supply requirement. Compared with traditional site power system, save 50% site footprint
- Unified power platform and key components with modular design, support smooth evolution for future 5G and low-carbon application
Efficient and Green
- Super high efficiency rectifier, peak efficiency≥97%, save more power loss during conversion process
- Support smooth solar access, MPPT units with 99.9% statistic tracking precision, make full utilization of solar resource, contributes to site carbon-neutral
- Voltage boosting for remote power supply, achieve 100% battery capacity utilization, and reduce cable loss
Smart Management
- Smart grid peak shaving, supports dynamic collaboration of rectifier and battery, achieve free grid modernization of site 5G evolution
- Smart metering, separated metering and billing for 3G/4G/5G device, achieve differential battery backup strategy to save investment cost
- Smart cloud management, achieves visible whole network site operation status view, provides O&M support guidance to reduce on-site visit, accurate energy efficiency analysis to improve network EE and save OPEX
Model | Parameter | |
---|---|---|
Model Type | ZXDUPA-CR01(V1.0) | |
AC Input Type | Three-phase five-wire (L1/L2/L3/N/PE) | |
Rectifier Power Density | 70.2 W/in3 | |
Rectifier Working Temperature | -40℃ ~75℃ | |
Rectifier Efficiency | Max. 97% | |
DC Lightning Protection | In: 10kA(8/20μS) for rectifier | |
Rectifier Rated Output Power | 4000W | |
Environment Interface | 4 for battery/ambient temperature(configurable), 1 for door magnetic, 1 for humidity, 1 for flooding and 1 for smoke | |
Relays (Dry Contacts) Interface | 8 for output dry contact, 8 for input dry contact | |
MTBF | ≥2*105 hours | |
Communication Interface | 1*RS232/RS485, 1*RS485, 1*FE, 1*USB | |
Rectifier Dimension | 40.8mm×84.5mm×292.5 mm(H×W×D) | |
CSU603A Dimension | 4U width, 1U height | |
AC Input | 85 AC- 300V AC@50 Hz / 60Hz | |
Altitude | 0 to 2000 m: 100% output power; 2000 to 3000 m: The power derating percentage is 1% when the altitude increases by 100 m. Customer shall use system under derating consideration. | |
Certification | EN61000,DIN/EN 55022,ETSI EN 300 386, IEC 61000,EN 55032, CISPR 32 UL/IEC/EN 62368. IEC 60950-22, EN 60950-22 IEC 60068, IEC 60529 GB/T 2423. 56-2006, IEC 60068-2-64:2008 | |
AC Lightning Protection | Class B+C 30kA (8/20μs) | |
Load Distribution | Flexible configuration, LLVD1:16poles LLVD2:12poles | |
Battery Distribution | 2×125A/1P MCBs | |
Output Voltage | -53.5VDC (-42VDC~-58VDC adjustable) | |
AC Input | 1*63A/4P MCB | |
Max. Capacity | 24kW, 6pcs rectifier at full configuration | |
Environment | Operating temperature: -10 ℃ to +45 ℃; Relative operating humidity: until 95 % (not condensing); Storage temperature: -40 ℃ to +70 ℃; Relative storage humidity: until 95 % (not condensing); Air pressure: 80kPA to 106kPA |