Products

Product Overview

ZXDUPA-CR01(V1.0)

Simpler Structure Design - Only need one cabinet to support 24KW output capacity and 2groups 12V Lead Acid battery or 4PCS 3U lithium battery, satisfy 3G/4G/5G co-site and sharing site power supply requirement. Compared with traditional site power system, save 50% site footprint - Unified power platform and key components with modular design, support smooth evolution for future 5G and low-carbon application

Highlights

Simpler Structure Design

- Only need one cabinet to support 24KW output capacity and 2groups 12V Lead Acid battery or 4PCS 3U lithium battery, satisfy 3G/4G/5G co-site and sharing site power supply requirement. Compared with traditional site power system, save 50% site footprint

- Unified power platform and key components with modular design, support smooth evolution for future 5G and low-carbon application

 

Efficient and Green

 

- Super high efficiency rectifier, peak efficiency≥97%, save more power loss during conversion process

- Support smooth solar access, MPPT units with 99.9% statistic tracking precision, make full utilization of solar resource, contributes to site carbon-neutral

- Voltage boosting for remote power supply, achieve 100% battery capacity utilization, and reduce cable loss

 

Smart Management

- Smart grid peak shaving, supports dynamic collaboration of rectifier and battery, achieve free grid modernization of site 5G evolution

- Smart metering, separated metering and billing for 3G/4G/5G device, achieve differential battery backup strategy to save investment cost

- Smart cloud management, achieves visible whole network site operation status view, provides O&M support guidance to reduce on-site visit, accurate energy efficiency analysis to improve network EE and save OPEX

Product Parameter

Model Parameter
Model Type ZXDUPA-CR01(V1.0)
AC Input Type Three-phase five-wire (L1/L2/L3/N/PE)
Rectifier Power Density 70.2 W/in3
Rectifier Working Temperature -40℃ ~75℃
Rectifier Efficiency Max. 97%
DC Lightning Protection In: 10kA(8/20μS) for rectifier
Rectifier Rated Output Power 4000W
Environment Interface 4 for battery/ambient temperature(configurable), 1 for door magnetic, 1 for humidity, 1 for flooding and 1 for smoke
Relays (Dry Contacts) Interface 8 for output dry contact, 8 for input dry contact
MTBF ≥2*105 hours
Communication Interface 1*RS232/RS485, 1*RS485, 1*FE, 1*USB
Rectifier Dimension 40.8mm×84.5mm×292.5 mm(H×W×D)
CSU603A Dimension 4U width, 1U height
AC Input 85 AC- 300V AC@50 Hz / 60Hz
Altitude 0 to 2000 m: 100% output power; 2000 to 3000 m: The power derating percentage is 1% when the altitude increases by 100 m. Customer shall use system under derating consideration.
Certification EN61000,DIN/EN 55022,ETSI EN 300 386, IEC 61000,EN 55032, CISPR 32 UL/IEC/EN 62368. IEC 60950-22, EN 60950-22 IEC 60068, IEC 60529 GB/T 2423. 56-2006, IEC 60068-2-64:2008
AC Lightning Protection Class B+C 30kA (8/20μs)
Load Distribution Flexible configuration, LLVD1:16poles LLVD2:12poles
Battery Distribution 2×125A/1P MCBs
Output Voltage -53.5VDC (-42VDC~-58VDC adjustable)
AC Input 1*63A/4P MCB
Max. Capacity 24kW, 6pcs rectifier at full configuration
Environment Operating temperature: -10 ℃ to +45 ℃; Relative operating humidity: until 95 % (not condensing); Storage temperature: -40 ℃ to +70 ℃; Relative storage humidity: until 95 % (not condensing); Air pressure: 80kPA to 106kPA