产品检索

Product Overview

W701 V6.0(One-Cabinet Site)

ZXDU68 W701 (V6.0) is ZTE new generation of outdoor DC power system, which can provide -53.5V DC power for communications equipment. It supports multiple energy resource utilization, including mains,diesel generator and solar. It has highly integrated structure design to save site footprint. Key components of the power system adopt modular design, support site smooth evolution from 4G to 5G with better CAPEX. Based on component-site-network 3 levels smart cloud management, whole network energy efficiency can be optimized and reduce the OPEX of O&M.

Highlights

Simpler Structure Design

- Only need one cabinet to support 700A output capacity and 900Ah battery backup capability, satisfy 3G/4G/5G co-site and sharing site power supply requirement. Compared with traditional site power system, save 50% site footprint

- Unified power platform and key components with modular design, support smooth evolution for future 5G and low-carbon application

- Multiple cabinet choice, adopts multiple large capacity cooling device like air-conditioner/ heat-exchanger/DC fan, satisfy heat dissipation requirement for 5G

 

Efficient and Green

 

- Super high efficiency rectifier, peak efficiency≥98%, save more power loss during conversion process

- Support smooth solar access, MPPT units with 99.9% statistic tracking precision, make full utilization of solar resource, contributes to site carbon-neutral

- Voltage boosting for remote power supply, achieve 100% battery capacity utilization, and reduce cable loss

 

Smart Management

- Smart grid peak shaving, supports dynamic collaboration of rectifier and battery, achieve free grid modernization of site 5G evolution

- Smart metering, separated metering and billing for 3G/4G/5G device, achieve differential battery backup strategy to save investment cost

- Smart cloud management, achieves visible whole network site operation status view, provides O&M support guidance to reduce on-site visit, accurate energy efficiency analysis to improve network EE and save OPEX

Learn more
Product_Parameter
Model Parameter(Operator) Parameter(Enterprise)
Model Type ZXDU68 W701 (V6.0)
AC Input Type Three-phase five-wire (L1/L2/L3/N/PE)  
Rectifier Power Density 48.8 W/in3  
Rectifier Working Temperature -40℃ ~75℃  
Rectifier Efficiency Max. 98%  
DC Lightning Protection In: 15kA(8/20μS) for rectifier  
Rectifier Rated Output Power 3000W  
Environment Interface 4 for battery/ambient temperature(configurable), 1 for door magnetic, 1 for humidity, 1 for flooding and 1 for smoke  
Relays (Dry Contacts) Interface 8 for output dry contact, 8 for input dry contact  
MTBF ≥2*105 hours  
Communication Interface 1*RS232/RS485, 1*RS485, 1*FE, 1*USB  
Rectifier Dimension 40.8mm×84.5mm×292.5 mm(H×W×D)  
CSU Dimension 2U width, 1U height  
AC Input 85 AC- 295V AC@50 Hz / 60Hz  
Altitude 0 to 2000 m: 100% output power; 2000 to 3000 m: The power derating percentage is 1% when the altitude increases by 100 m. Customer shall use system under derating consideration.  
Certification IEC60950,IEC61000,EN55032 Class A, IEC 61000  
AC Lightning Protection Class II, In: 20kA(8/20μS)  
Load Distribution Flexible configuration,LLVD1: 6 ways,LLVD2/BLVD: 6 ways  
Battery Distribution 3×125A/2P MCBs  
Output Voltage -53.5VDC (-42VDC~-58VDC adjustable)  
AC Input 1*125A/3P MCB  
Max. Capacity 42kW, 14pcs rectifier at full configuration
Product Recommendation